5801 Control Faceplate: 

5801 Control Faceplate IntelliTEAM II Software B. Dicke O2 - IT II Faceplate 5801 with Audio 11-04-09 Press Pg Dn to Start the Program

PowerPoint Presentation: 

Serious risk of personal injury or death may result from contact with electric distribution equipment when proper isolation and grounding procedures are not followed. The equipment described in this presentation must be operated and maintained by qualified persons who are thoroughly trained and understand any hazards involved. This information presented herein is intended only as a supplement to equipment instructions for such qualified persons and is not a substitute for adequate training and experience in safety procedures for accessing high voltage equipment. Any conflict between the information in this presentation and utility practices should be reviewed by appropriate utility personnel and a decision made as to the correct procedures to follow. Disclaimer on Content Conflicts

PowerPoint Presentation: 

This is a confidential presentation developed by S&C Electric Company for use exclusively in company presentations. Data and statistics used were generated from private surveys or publicly available data published in the industry literature. Copies of this PowerPoint presentation are being offered to interested utilities for their internal use only. Other uses or modifications to this material are unauthorized. Copyright © 2009 All rights reserved. Limitation of Copy Distribution

PowerPoint Presentation: 

5 IntelliTEAM II 5801

PowerPoint Presentation: 

6 IntelliTEAM II 5803

PowerPoint Presentation: 

7 5802 in Pad-Mounted Gear IntelliTEAM II

PowerPoint Presentation: 

5802 in VISTA IntelliTEAM II

PowerPoint Presentation: 

9 LCD Display RDY = Team in READY ALM = Team in ALARM FLT = Fault in Team Shows other data selected by DATA SCROLL switches IntelliTEAM II 5801

PowerPoint Presentation: 

LCD Display IntelliTEAM II 5801 The RDY indicator shows that the teams are ready to transfer

PowerPoint Presentation: 

11 Data Scroll Change the data in the LCD display See the data scroll guide Left - right gets in the correct column Up - down gets on the correct line IntelliTEAM II 5801

PowerPoint Presentation: 

12 Data Scroll Left - right gets in the correct column Up - down gets on the correct line IntelliTEAM II 5801

PowerPoint Presentation: 

13 Fault Light On for a fault Off for a closed switch when 3 phase voltage returns and after 45 minutes Off for a normally open switch when toggle remote / local IntelliTEAM II 5801

PowerPoint Presentation: 

14 XMT / RCV Lights Communication to other team members or SCADA XMT = Transmit RCV = Receive 2 Ports - may use only 1 Need both XMT and RCV to communicate IntelliTEAM II 5801

PowerPoint Presentation: 

15 Error Light Battery charger over voltage Unknown switch position Temperature sensor failure Software problem IntelliTEAM II 5801

PowerPoint Presentation: 

16 Status Light Blinking = OK IntelliTEAM II 5801

PowerPoint Presentation: 

17 Battery Light & Switch Off = Battery is OK On = Replace battery Blinking = Battery test in progress Done once a day Push battery test switch up to start a test IntelliTEAM II 5801

PowerPoint Presentation: 

18 Battery Light & Switch Push battery test switch down to test all lights IntelliTEAM II 5801

PowerPoint Presentation: 

19 Computer Connection DB 9 connector Straight-through serial cable (not null modem) IntelliTEAM II 5801

PowerPoint Presentation: 

20 Close, Trip, Open Closed, Open lights show the position of the line switch Trip light - Automatic operation has opened the line switch Toggle switch will operate the line switch if remote / local switch is in local IntelliTEAM II 5801

PowerPoint Presentation: 

21 Local / Remote Remote = SCADA can operate the line switch, but toggle switch can not Local = Toggle switch can operate the line switch, but SCADA can NOT Light is on IntelliTEAM II 5801

PowerPoint Presentation: 

22 Local / Remote TEAM OPERATION CAN HAPPEN IN EITHER LOCAL OR REMOTE IntelliTEAM II 5801

PowerPoint Presentation: 

23 Enable / Disable Indicator Light Switch enables or disables control if local / remote switch is in local Disabled stops all automatic operation and takes team out of READY IntelliTEAM II 5801

PowerPoint Presentation: 

Working on a Line with IntelliTEAM Controls 1. Control in LOCAL 2. Control in DISABLE 3. Get a VISUAL OPEN 4. GROUND At each TEAM Member: These are recommendations. Please observe local operating practices which take precedent IntelliTEAM II 5801

PowerPoint Presentation: 

Return to Automatic Operation Remove Grounds Control in Remote Close Visual Open At last switch wait Control In Local for RDY indication Switch line switch to original position Disable / Enable to Enable At each end of the line: IntelliTEAM II 5801 These are recommendations. Please observe local operating practices which take precedent

PowerPoint Presentation: 

26 Enabling Shots to Lockout on a Closed Line Switch Close a Line Switch Using the Shots to Lockout Feature IntelliTEAM II 5801

PowerPoint Presentation: 

Swing Panel Open 4 Lights ON Red Analog Power Battery Charger AC Power Yellow Battery Connected

PowerPoint Presentation: 

1 Light OFF Red Cal = Calibrate Swing Panel Open

PowerPoint Presentation: 

UtiliNet Radio Light Blinking Red Every 2 sec – Radio on and operational Every 1 sec – Radio on, operational, and communicating with another radio Swing Panel Open

PowerPoint Presentation: 

30 SPA Board ASP Board PS/IO Processor Communication Plate Board Identification

PowerPoint Presentation: 

31 Questions ? Tech Support Call (773) 338-1000 Southeast Ext 3120 West Ext 3121 East-East Central Ext 3122 West Central Ext 3123 International Ext 3124 Canada Ext 3125