Clamp-on Power Meter CW240 :Clamp-on Power Meter CW240 New! The CW240 Finds
your power quality problems!
Contents :Contents 1. Purpose of development
2. Position of CW240
3. Characteristics of CW240
1) Characteristics
2) Power management
3) Power Quality management
4) Meas. Phase/wiring
5) Multi wiring system
6) Leak current measurement
7) Analog I/O
8) Wiring & Wiring Check
9) Function
4. Comparison vs. Other CW series
5. Comparison vs. Hioki
CW Series :CW Series Power Quality Measurement CW340 ?
DC + Inverter? Energy Saving Measurement To reduce Electric power To solve power quality problem CW1000?
PQA?
Characteristics 1 :Characteristics 1 Electric Power Search & PQ Management Harmonics Simultaneous measurement of All items and save all data Demand Electric Energy Voltage Fluctuation Instantaneous Value
Characteristics 2 :V Range : 150/300/600/1000V
A Range : Minimum 200.0mA(96036)
Maximum 3000A (96034/35)
Measuring Mode: All items can be measured at the same time
Instantaneous Value (Wave form) / Electric Energy /
Demand / Harmonics / Voltage Fluctuation
Wiring 1 phase 2W, 1 phase 3W, 1 phase 3W3i (Neutral line current)
3 phase 3W2i, 3 phase 3W3i, 3 phase 4W,
3 phase 4W4i (Neutral line current)
Multiple System Load Measurement:
1 phase 2W X2/ X3/ X4, 1 phase 3W X2, 3 phase 3W X2,
Data Saving: PC Card, Internal Memory (1MB)
Data Saving Interval:
Standard 1/2/5/10/15/30 sec 1/2/5/10/15/30/60 min
Short time 1 Cycle/0.1/0.2/0.5 sec (Only for Instantaneous Value)
Function:
Leak Current
Analog I/O
Wiring & Setting Check
Display Hard Copy, Instantaneous Value Data Saving Characteristics 2
Electric Power Management 1 :Electric Power Management 1 -Display Instantaneous Value for each measurement item
Each Phase Voltage/Current/Electric Power/Power Factor/Frequency /Phase Angle/Reactive Power/Apparent Power
-Mean/Min/Max display for each measurement element
-Standard interval of data Saving cycle starts from 1 second
1/2/5/10/15/30 sec, 1/2/5/10/15/30/60 min Instantaneous Value Measurement 1 45~65Hz
Electric Power Management 2 :Wave form display can be possible with short time interval
1 cycle (1 wave form) /0.1/0.2/0.5 sec
-Measuring elements: Voltage, Current, Voltage & Current
-Max 20 times zoom for vertical axis ( X1/3, X1/2, X1, X2, X5, X10, X20)
-Data saved by binary form Electric Power Management 2 Instantaneous Value Measurement 2 V&A Waveform Current Waveform Voltage Waveform
Electric Power Management 3 :-Data Acquisition Time: 1/2/5/10/15/30 sec. 1/2/5/10/15/30/60 min.
-Measuring Elements: Active power energy, Regenerative electric power energy, Lag reactive energy, Lag, Lead reactive energy
-Measurement Range:
Active Power Energy: Consumption 0.00000mWh ~ 999999GWh
Regenerative -0.00000mWh ~ -999999GWh
Reactive Power Energy: Lag 0.00000mvarh ~ 999999Gvarh
Lead -0.00000mvarh ~ -999999Gvarh Electric Energy Measurement Electric Power Management 3
Electric Power Management 4 :-MAX Demand and Display its occurrence time
-Measuring Elements: 1) Active Power, Reactive Power (Dead Time),
Power Factor,
2) Active Power Energy (Consumption & Regenerative), Reactive Power Energy (Lead & Lag)
3) MAX Demand value from the beginning of logging measurement, and Occurrence time Demand Measurement Electric Power Management 4
Slide 10:-Harmonics Analysis : 1 to 50th order
-Display Data : List/Bar Graph(Linear/Log)/Vector
-Measuring Elements : RMS Value/Content/Phase angle(Voltage for each order/Current/Electric Power)
-Total Value(Total value of Voltage, Current, Electric power and Power factor)
-Total relative harmonic content (Voltage, Current, THD-H or THD-R) Harmonics Measurement RMS Content Phase angle Changeable Linear/Log Electric Power Management 5
3.-3. Power Quality Management :3.-3. Power Quality Management -Voltage Dip, Voltage Swell and detect instantaneous power failure
-Save data for Data of detection, Item, Channel, RMS and Detection period
*Set threshold for voltage, and record when the value is going out of the set threshold Voltage fluctuation Date Item
Swe:Swell
Dip:Dip
Int:Inst. Power failure Channel 0:Occurrence
1:End RMS Detected period
3.-4. Phase & Wiring Measurement :3.-4. Phase & Wiring Measurement 3 Phase 3 Wire Add 3 current (3 wattmeter method)
Measure current of each phase
Measure each line voltage
1 Phase 3 Wire 3 Current / 3 Phase 4 Wire 4 Current
Can be measure neutral line current(N Phase : Leak Current)
→Use CH4 to set Probe/Range 1P3W3i 3P4W4i Power supply Load Power supply Load
3.-5.Multi System Measurement(1/3) :3.-5.Multi System Measurement(1/3) -Simultaneous measurement of 1 phase 2W X4 system load
(Common Voltage)
-Clamp probe is settable for each system/Clamp Probe
for each system load/Can be set current range 1 Phase 2W X 4 system measurement Power supply Load Load Load Load
3.-6. Leak Current Measurement :3.-6. Leak Current Measurement Leakage current measurement 2A Clamp Probe (96036) new release
200.0mA Range External magnetic field effect is
less than 0.002A 1) Leakage current measurement for 1 to 4CH
2) When measuring 1 phase 3W3i or 3 phase 4W4i,
3) Possible to set Clamp/Range for CH4 (individual) Φ40mm uses 30031 sensor technology Setting is different from Ch1 to Ch3 Load Load Power supply
3.-7.Analog input/output :3.-7.Analog input/output Analog Output Data can be collected with electric power data (Range:100mV/1V/5V) 4CH output + 2CH input Temp/Lux/Flow/Pressure CW240 Voltage, Current, electric power etc. Analog Output Data from Thermometer/Lux meter which related to power measurement can be collected by CW240 4ch:±1VDC
3.-8. Wiring & Setting Check(1/2) :3.-8. Wiring & Setting Check(1/2) Check suitability of V/A input value, V/A phase difference, Phase difference between voltage, Phase difference between Current and Frequency
Wiring Chart、Vector Chart display Wiring Check Function Voltage/Current input value Vector Diagram Reduce wiring error before the measurement!
3.-8.Wiring & Setting Check(2/2) :3.-8.Wiring & Setting Check(2/2) Setting Check Function Phase/Range etc. Can check setting condition with the display
If you find mistake, you can go to setting display just by pushing setting button Saving Item Start/End Measurement Prevent measurement failure and wiring error!
3.-9.Function(1/2) :3.-9.Function(1/2) Display Hardcopy, Instantaneous value Data Saving (1 push of button)
Display Hardcopy(BMP format)
Can save instantaneous value
Standard: CSV format
Short period: Binary format
Prevent incorrect connection of Clamp Probe
(Also prevents connection of voltage probe)
Magnification function for the display
Displays magnification for set item
Available for instantaneous value & electric power
measurement item
Backup Power Supply
Besides AC adapter, CW240 accepts NiMH battery,
AA alkaline battery (x6)
Multi Language display
English/French/Spanish/Italian/German and Japanese Instantaneous value fining Display Hardcopy
3.-9. Function(2/2) :3.-9. Function(2/2) Software : ToolBox240
(Setting & Data Conversion Software)
1) Setting of the main unit
2) Binary format
(Convert waveform data to CSV format)
3) File Segmenting
4) 6 languages for the display Data will be saved in memory card or internal memory Data
4.Comparison vs. CW140 :4.Comparison vs. CW140
5.Comparison vs. Competition :5.Comparison vs. Competition
5. Comparison vs. Competition :5. Comparison vs. Competition Good Points of CW240
1. Power Quality (Dip/Swell & 50th Order
Harmonics )
2. Leak Current Measurement(No effect from external
magnetic field)
3. Analog input/output
4. Commonly used Clamp Probe
5. Vector display of wiring error check
6. Data memory save/Waveform display start from
1 cycle
7. Easy operation
Slide 23:SP price for CW240 (3P4W setting)
CW240 + 96030 x 3 + Carrying Case + Memory CARD(32MB) + NiMH battery
= US$2,740 6.Pricing