Advanced Protection Technologies Overview of UL 1449 Third Edition Narrated by: Robert Stanley

Surge Protection.. : 

2 Surge Protection.. MOV/SPD Load ..in ACTION!

Surge Protection.. : 

3 Surge Protection.. MOV/SPD Load ..in ACTION!

UL 1449 THIRD Edition : 

UL 1449 THIRD Edition Safe Surge Protection Specification Interpretation Ordering Procedures Product Applications Next Generation of SPD Products and Features Our Services and Support Today you will leave here knowing….

UL 1449 THIRD Edition : 

UL 1449 THIRD Edition SPD TVSS Surge Arresters Combine TVSS and Surge Arresters into one UL Standard, UL 1449 3rd Edition renamed: Surge Protective Devices (SPDs) Effective: Sept 29, 2009 New SPD Types: Types 1, 2, 3 & 4 New Voltage Protection Ratings (VPRs) replace old-style Suppressed Voltage Ratings (SVRs) New I nominal ratings Bid Specifications become Obsolete as product evaluation & ratings change

UL 1449 THIRD Edition & 2008 NEC Art 285 : 

6 UL 1449 THIRD Edition & 2008 NEC Art 285 Changing term TVSS to SPD TVSS SPD Creates Types 1, 2, 3 & 4 SPDs Type 1 – Installed on line or load side of Main OCP - similar to what you knew as SSA, except now includes rigorous safety testing. Includes all OCP & safety apparatus inside SPD Type 2 – Installed on load side of Main OCP - similar to what you know as hardwired TVSS. May require external OCP Type 3 – Point of Utilization – direct plug in - similar to what you know as surge strips - 10 meters from panel (rational based on being IEEE Cat. A location) Type 4 – surge suppression components, could be basic component or complete module. Type 4 components can be tested for Type 1, Type 2 or Type 3 applications. X X

UL 1449 THIRD Edition & 2008 NEC Art 285 : 

7 UL 1449 THIRD Edition & 2008 NEC Art 285 Changing term TVSS to SPD TVSS SPD Creates Types 1, 2, 3 & 4 SPDs Type 1 – Installed on line or load side of Main OCP - similar to what you knew as SSA, except now includes rigorous safety testing. Includes all OCP & safety apparatus inside SPD Type 2 – Installed on load side of Main OCP - similar to what you know as hardwired TVSS. May require external OCP Type 3 – Point of Utilization – direct plug in - similar to what you know as surge strips - 10 meters from panel (rational based on being IEEE Cat. A location) Type 4 – surge suppression components, could be basic component or complete module. Type 4 components can be tested for Type 1, Type 2 or Type 3 applications. X X

Slide 8: 

UL 1449-3 & 2008 NEC Art 285 SPD Types: Types 1, 2, 3 & 4 Based on Location within electrical distribution system Trans Meter Svc. Disc. Panel Type 1 10m (30feet) Type 2 Type 3 OCP built in to SPD, more rigorous testing

UL 1449 THIRD Edition : 

9 UL 1449 THIRD Edition Performance Test Format Changed New Testing uses Six (6) Times More Energy Old – 6kV / 500A Suppressed Voltage Ratings (SVR) New – 6kV / 3,000A Voltage Protection Ratings (VPR) 500A 3000A As surge amplitude goes up, clamping voltage goes up too Specs become obsolete Need new VPRs in specs

New Clamping Voltages : 

New Clamping Voltages

UL 1449 THIRD Edition : 

UL 1449 THIRD Edition I nominal Testing – In - (Nominal Discharge Current) - New Concept to USA – Originated from IEC 61643 - Duty Cycle Testing - 15 8x20s surges through every mode of three samples used for VPR testing Type 1 – 20kA or 10kA Type 2 – 20kA, 10kA, 5kA or 3kA Type 3 – 3kA Type 4 – Based on intended usage as Types 1, 2 or 3 UL 96A Master Label requires 20kA In from Type 1 or Type 2 SPD

What to look for in a spec…. : 

What to look for in a spec….

…continued : 

…continued

Slide 14: 

APT offers a full breadth of Type 1 and Type 2 SPD’s. Our Type 1 SPD’s use Large Block 50kA MOV’s that have Thermal Protection and are very reliable and robust. Each Series offers protection which is ideal for remote locations and extreme duty applications where downtime is unacceptable, to models ideal for downstream applications. Our units offer protection from 50kA per phase up to 1000kA per phase. Advanced Protection Technologies

SPD Products from Advanced Protection Technologies : 

SPD Products from Advanced Protection Technologies Low UL 1449 Third Edition VPRs – Voltage Protection Ratings SCCR tested to 200kA and service entrance (C High - C3) rated “Always On” diagnostics with audible alarm that continuously monitor SPD unit status AC tracking filter with EMI/RFI Filtering up to -50db from 10kHZ to 100MHZ 10 Year Warranty* (Also available in 20 & 30) *Does NOT include SPDee or DIN Rail* Unitized Replaceable Module DIN Rail

XB SeriesDependable protection at Service Entrance, Distribution Panels and Downstream : 

XB SeriesDependable protection at Service Entrance, Distribution Panels and Downstream Redundant Suppression Modules (2 per phase). XBS: Standard modes (L-N, L-G, L-L, N-G) XBL: Includes direct L-L protection for 10 mode Wye Systems (L-N, L-G, L-L, N-G) Surge current ratings of 400kA, 500kA, 600kA, 1000kA per Phase (XBL 10 Mode: 600 or 900kA) Internal Disconnect Switch: Standard All Overcurrent Protection included inside SPD Options: Dry Contacts, Surge Counter Standard Enclosure: NEMA 1, 12, 3R, 4 Optional Enclosures: 4S, 4X, FM UL Recognized Case-less model for switchboard and switchgear mounting (See XW Series) 200kA & 100kA SCCRs UL & NEC Type 1 SPD 20kA In Rating (Nominal Discharge Current) EMI/RFI Noise Filtering

XA SeriesFor Critical Loads at Service Entrance Switchboards/Switchgear : 

XA SeriesFor Critical Loads at Service Entrance Switchboards/Switchgear XAS: Standard modes (L-N, L-G, L-L, N-G) XAL: Includes direct L-L protection for 10 mode Wye Systems (L-N, L-G, L-L, N-G) Surge current ratings: 100kA, 150kA, 200kA, 250kA, 300kA, 400kA, 500kA per Phase Internal Disconnect Switch: Optional All Overcurrent Protection included inside SPD Options: Dry Contacts, Surge Counter Standard Enclosure: NEMA 1, 12, 3R, 4 Optional Enclosures: 4S, 4X, FM UL Recognized Case-less model for switchboard and switchgear mounting (See XR & W Series) 200kA & 100kA SCCRs UL & NEC Type 1 SPD 20kA In Rating (Nominal Discharge Current) (Most models) EMI/RFI Noise Filtering

Slide 18: 

TE/XGA Series Full Featured workhorse for service entrance, distribution and branch panels. All modes: L-N, L-G, L-L, N-G Surge current ratings: 160kA, 240kA per Phase Optional Hybrid MOV/SAD: 90kA, 130kA, 170kA per Phase All Overcurrent Protection included inside SPD Options: Dry Contacts, Surge Counter Standard Enclosure: NEMA 1, 12, 3R, 4 Optional Enclosures: 4S, 4X, FM UL Recognized Case-less model for switchboard and switchgear mounting (See XTE/XGA Series) 200kA SCCR UL & NEC Type 2 SPD TranSafe Redundant Circuitry Large Block 40kA MOVs EMI/RFI Noise Filtering

Slide 19: 

TE/HP TE/HP Series Dependable protection at service entrance, distribution panels and downstream. All modes: L-N, L-G, L-L, N-G Surge current ratings: 120kA, 160kA per Phase Phase Replaceable Modules Phase Replaceable Fuses All Overcurrent Protection included inside SPD Options: Dry Contacts, Surge Counter Standard Enclosure: NEMA 1, 12, 3R, 4 Optional Enclosures: 4S, 4X, FM UL Recognized Case-less model for switchboard and switchgear mounting (See XTE/HP Series) 200kA SCCR UL & NEC Type 2 SPD Large Block 40kA MOVs EMI/RFI Noise Filtering

Slide 20: 

TE/HPS TE/HPS Series Budget conscious protection for service entrance, distribution and branch panels. All modes: L-N, L-G, L-L, N-G Surge current ratings: 80kA, 120kA & 160kA per Phase Phase Replaceable Modules Phase Replaceable Fuses All Overcurrent Protection included inside SPD Options: Dry Contacts Standard Enclosure: NEMA 1, 12, 3R, 4 Optional Enclosures: 4S, 4X, FM UL Recognized Case-less model for switchboard and switchgear mounting (See XTE/HPS Series) 200kA SCCR UL & NEC Type 2 SPD Large Block 40kA MOVs EMI/RFI Noise Filtering

XDS SeriesFor Distribution and Branch Applications : 

XDS SeriesFor Distribution and Branch Applications All modes: L-N, L-G, L-L, N-G Surge Current Ratings: 100kA, 150kA, 200kA Per Phase Enclosure: NEMA 4X Standard Options: Dry Contact & Audible Alarm Delete Noise Filtering FM – Flushmount UL & NEC Type 1 SPD 20kA In Rating (Nominal Discharge Current) (Most Models) EMI/RFI Noise Filtering

XCS SeriesFor Branch Panel Applications : 

XCS SeriesFor Branch Panel Applications All modes: L-N, L-G, L-L, N-G Surge Current Rating: 100kA per phase Enclosure: NEMA 4X Standard Options: Dry Contact & Audible Alarm FM – Flushmount UL & NEC Type 1 SPD 20kA In Rating (Nominal Discharge Current) (Most Models)

SPDEE Series : 

SPDEE Series Versatile – Numerous voltage configurations: 1Pole, 2 Pole (Split Phase), 3 Phase 50kA or 100kA (Split-Phase) Per Phase Always On Green LED Options N-G protection Dry Contact & Audible Alarm Other configurations available for OEM – Call Tri-Mount Installation Nipple Din-Rail Backplane UL & NEC Type 1 SPD Replaces Secondary Arrestors Meets UL 96A Lightning Protection Master Label @ 20kA In 20kA In Rating (Nominal Discharge Current) (Most models)

APT DIN Rail Surge Protection Devices : 

APT DIN Rail Surge Protection Devices APT AC DIN Rail mounted SPDs are designed for downstream load protection. They are parallel connected devices which utilize large block MOVs, housed in UL 94V-0 thermoplastic enclosures. Each device includes internal thermal disconnects and visual failure mode status indicators with optional relay contacts. These devices are intended for use in IEC Class II, UL 1449 Type 2, Type 4, and IEEE Category C, B & A load applications.. APT Low Voltage DIN Rail SPDs utilize a hybrid mix of Tranzorbs, inductors, gas tubes, and resistors for complete low-voltage/data protection. These products are intended for use on a wide range of low-voltage applications, protect up to 4 wires in a single enclosure, adhere to UL 497B and are IEC / CE compliant. Offered in a full range of AC service voltages; 120V Single Phase 120/208V 3-Phase Wye 120/240V Split Phase 480V 3-Phase Delta 230V Single Phase 277/480V 3-Phase Wye 240V 3-Phase Delta 347/600V 3-Phase Wye 277V Single Phase The following DC low voltage are also available: 5V / 4-wire 12V / 4-wire 24V / 4-wire 48V / 4-wire 60V / 4-wire

Qualifying things to know: : 

Qualifying things to know: System Voltage Panel Information Panel Amperage ?

Qualifying things to know: : 

Qualifying things to know: System Voltage Panel Information Panel Amperage Available Breaker SPD Options ?

Slide 27: 

APT SPD - Ordering

Verifying at www.UL.com : 

28 Verifying at www.UL.com Click Certifications Category Code #’s: XUHT for TVSS (<Oct 09) OWHX for Arrestors (<Oct 09) VZCA for SPDs

APT – the answer to all your surge protection needs!!! : 

APT – the answer to all your surge protection needs!!! Some of our services include: Competitor Product Comparison – Competitively priced in the current market Proper Product Selection – Based on specification/engineer requirements Specification Interpretation with Engineering Assistance Consulting Engineering History – Extensive database, compiled over the last 25 years, we know engineers likes/dislikes Never sell direct to contractors – You deal direct with the factory Submittals – E-mailed in minutes Experience in the Industrial Market - New Din Rail Products Live Interactive Internet Based Training – Seminars also hosted here at our factory Stocking Program – No minimums or penalties Troubleshooting, Returns APT: 800.237.4567www.apttvss.com, www.aptspd.com