Engineering : Engineering Design Issues for Essential Facilities and Shelters


Florida Emergency Operations Centers Design and Evaluation Criteria : Florida Emergency Operations Centers Design and Evaluation Criteria Danny Kilcollins, FPEM Planning Manager Division of Emergency Management


Features of a Survivable EOC : Features of a Survivable EOC


Minimum Hurricane Safety Criteria for Critical Facilities : Minimum Hurricane Safety Criteria for Critical Facilities


ARC 4496 Hurricane Hazards : ARC 4496 Hurricane Hazards Wind Storm Surge Flooding Rainfall Flooding Hazardous Materials


High Performance Design Criteria: DOE-STD-1020 : High Performance Design Criteria: DOE-STD-1020


DOE-STD-1020 Natural Hazards : DOE-STD-1020 Natural Hazards Wind Flooding Earthquake


Hurricane Wind Design : Hurricane Wind Design


DOE 1020 Wind Design : DOE 1020 Wind Design


Return Period Years : Return Period Years


ASCE 7-02 : ASCE 7-02


Florida Building Code – Basic Wind Speeds and Windborne Debris Impact Regions : Florida Building Code – Basic Wind Speeds and Windborne Debris Impact Regions


Basic Wind Speed Conversions : Basic Wind Speed Conversions


1,000-yr Return Period : 1,000-yr Return Period


1,000-yr Recurrence Wind Speeds for Florida : 1,000-yr Recurrence Wind Speeds for Florida


Fla. PC 3 Wind Design Criteria : Fla. PC 3 Wind Design Criteria


TORNADO EVENTS IN FLORIDA : TORNADO EVENTS IN FLORIDA F0


10,000-yr Return Period : 10,000-yr Return Period


10,000-yr Recurrence Wind Speeds for Florida : 10,000-yr Recurrence Wind Speeds for Florida


Fla. PC 4 Wind Design Criteria : Fla. PC 4 Wind Design Criteria


Probable Minimum Central Pressure Limit Estimate for Hurricanes : Probable Minimum Central Pressure Limit Estimate for Hurricanes


Probable Minimum Central Pressure Limit Estimate for Hurricanes; Source: K. Emanuel (1996) : Probable Minimum Central Pressure Limit Estimate for Hurricanes; Source: K. Emanuel (1996)


Minimum Central Pressure to Wind Velocity Conversion : Minimum Central Pressure to Wind Velocity Conversion Source: Hurricanes and Typhoons: Past, Present and Future; Landsea, etal 880 mb = 190 mph (232 mph, 3-sec gust) 885 mb = 185 mph (226 mph, 3-sec gust) 890 mb = 180 mph (220 mph, 3-sec gust) 900 mb = 170 mph (208 mph, 3-sec gust) 910 mb = 165 mph (202 mph, 3-sec gust)


Windborne Debris Impact Resistance Criteria : Windborne Debris Impact Resistance Criteria


Representative Wind Design Criteria : Representative Wind Design Criteria Applies to the EOC and essential ancillary structures and service equipment Wind Load Design per ASCE 7 Standard Minimum Design Wind Speed = 190 mph, 3-second gust Wind Importance Factor, I=1.00 Exposure Category = C Directionality Factor, Kd=1.00 Internal Pressure Coefficient, GCpi= +/-0.18


Representative Wind Design Criteria : Representative Wind Design Criteria The EOC designated as a threshold building, and special structural inspections required Special inspections conducted in compliance with section 553.79, Florida Statutes and other applicable statutes, laws and rules


Representative Wind Design Criteria : Representative Wind Design Criteria Design Windborne Debris Missile = 15 lb 2x4 propelled at 50 mph (74 ft/sec) 34 lb-sec of momentum Design missile applies to all exterior enclosure components, claddings and assemblies (i.e., walls, roofs, louvers, windows, doors, etc.) Design missile applies to enclosure surfaces located within 60 feet in height above finish grade


Summary of Wind Storm Design Criteria : Summary of Wind Storm Design Criteria


Comparison of Hurricane Wind Codes & Standards : Comparison of Hurricane Wind Codes & Standards


Tornado Wind Design : Tornado Wind Design


FEMA 361 – Tornado Winds : FEMA 361 – Tornado Winds


FEMA 361 Wind Zones : FEMA 361 Wind Zones


TORNADO EVENTS IN FLORIDA : TORNADO EVENTS IN FLORIDA F0


Flood & Rainfall Design : Flood & Rainfall Design


DOE 1020 Flood Criteria : DOE 1020 Flood Criteria


NOAA HMR No. 51 and No. 52 Probable Maximum Precipitation Estimates : NOAA HMR No. 51 and No. 52 Probable Maximum Precipitation Estimates


24-hour PMP @ 10 sq.mi. Basin : 24-hour PMP @ 10 sq.mi. Basin


72-hour PMP @ 10 sq.mi. Basin : 72-hour PMP @ 10 sq.mi. Basin


Max. Observed Point Rainfall Illustration Source: Unknown : Max. Observed Point Rainfall Illustration Source: Unknown


Estimated 24-hour Rainfall Rates w/Recurrence Intervals : Estimated 24-hour Rainfall Rates w/Recurrence Intervals


Conversion of 10 sq.mi. PMPs to 1 sq.mi. PMPs : Conversion of 10 sq.mi. PMPs to 1 sq.mi. PMPs


1-hour PMP @ 1 sq.mi. Basin : 1-hour PMP @ 1 sq.mi. Basin


Estimated 1-hour Rainfall Rates w/Recurrence Intervals : Estimated 1-hour Rainfall Rates w/Recurrence Intervals


Summary of Flood Design Criteria : Summary of Flood Design Criteria


Summary of Flood Design Criteria : Summary of Flood Design Criteria


Storm Surge Flooding : Storm Surge Flooding SLOSH Storm Surge Model Category 5 inundation depth/elevation, NGVD Maximum Envelope of Water Margin of Error = +/- 20% Category 5 elev. + 20% = Probable Maximum Inundation


Storm Surge Flooding : Storm Surge Flooding Fla. Performance Category 3 = Cat. 5 + 15% Fla. Performance Category 4 = Cat. 5 + 20% Performance suggested per county based on PC 4 (10,000-yr) Wind Map Design wind speeds at coast that are greater than or equal to 190 mph (3-sec. gust) = Cat. 5 + 20% Design wind speeds at coast that are less than 190 mph (3-sec. gust) = Cat. 5 + 15%


Representative Flood Design Criteria : Representative Flood Design Criteria Applies to lowest floor for the EOC and essential ancillary structures and service equipment Finished Floor Elevation NGVD determined by: Category 5 storm surge elev. + 20% BFE + 3.0 feet 500-yr elevation + 2.0 feet Highest recorded flood elevation + 3.0 feet Whichever flood elevation is highest


Representative Flood Design Criteria : Representative Flood Design Criteria The site (point maximum, one square mile) hydrologic design shall ensure that the EOC and essential ancillary structures and service equipment are not flooded due to a 24 hour, 37.0 inch rainfall event applied over a precedent 24 hour, 100-year rainfall event Opinion of design professional is acceptable Basin-wide analysis not required


Representative Flood Design Criteria : Representative Flood Design Criteria Where secondary (emergency) roof drains or scuppers are required by the Florida Building Code—Plumbing, the secondary system shall be sized for a rainfall rate of eleven (11.0) inches per hour


Earthquake Design : Earthquake Design


Earthquake 10,000-yr Design Criteria for Florida : Earthquake 10,000-yr Design Criteria for Florida


Earthquake 10,000-yr Design Criteria for Florida : Earthquake 10,000-yr Design Criteria for Florida


Anti-Terrorism Design : Anti-Terrorism Design


USAF Installation Force Protection Guide : USAF Installation Force Protection Guide


Is Blast Hardening Req’d? : Is Blast Hardening Req’d?


Minimum Anti-Terrorism Standards for Buildings : Minimum Anti-Terrorism Standards for Buildings


Design of Buildings to Resist Progressive Collapse : Design of Buildings to Resist Progressive Collapse


FEMA CPG 1-20 / May 1984 : FEMA CPG 1-20 / May 1984


FEMA CPG 1-20 EOC Staff Size Estimate/ Community Size : FEMA CPG 1-20 EOC Staff Size Estimate/ Community Size


FEMA CPG 1-20 EOC Staff Size Estimate/Community Size : FEMA CPG 1-20 EOC Staff Size Estimate/Community Size


Electrical Power Restoration : Electrical Power Restoration