Testing Test Setup TapLok Insert Shear Key Copper Threads Friction Tests Collar Shear Tests NSTX TF FLAG JOINT REVIEW 8/7/03 Michael Kalish

Test Setup: 

Test Setup MTS Hydraulic Test Stand Plots Load vs Deflection up to 100,000 lbf Provides Cyclical Testing Capabilities

TapLok Pull Tests: 

TapLok Pull Tests Objective: To determine pull out strength as well as to prove durability of insert over 50,000 cycles TapLok Inserts installed in spare lengths of conductor Test samples prepared to be identical to actual conductor

Slide4: 

Flag Stud Inserts

TapLok Pull Tests: 

TapLok Pull Tests Specimen in Test Fixture

TapLok Pull Tests: 

TapLok Pull Tests Static tests were performed on KeenSerts and both .687” and .562” long TapLok Inserts (13 TapLoks & 8 KeenSerts) The design settled on the .562” TapLoks and results presented are only that insert Only .562” long TapLoks were cycled Average pullout force for .562” TapLok was 12,700 lbf with a corresponding ultimate shear stress of 29.9 KPSI (compares conservatively with design allowables)

Static Pull Test Plot: 

Static Pull Test Plot Displacement vs Force Curve for Tap Lok #4, 3rd Sample Peak Force = 12,500 lb A graph of force vs deflection is generated for each sample

Slide8: 

TapLok Static Pull Test Results

Cyclical Testing, TapLok: 

Cyclical Testing, TapLok Using same test setup medium length (.562”)Tap Lok inserts were cycled then pulled Test pieces were cycled at 5,000 to 6,000 lbf for 50,000 cycles or greater Test sample was heated to 100 C during cycling Cycled with 1 Hz Sine Wave Thermal loading accounts for 83% of the cyclical load Thermal loading occurs for only approximately 1,000 of the 50,000 cycles but testing applied full loading for all 50,000 cycles

Cyclical Testing Plot: 

Cyclical Testing Plot Example of force vs deflection curve for cycling of inserts Shaded area may indicate drift or creep (first run exhibited a “negative creep” drift)

Cyclical vs Static Pull Test: 

Cyclical vs Static Pull Test Fatigued Insert Pullout (bottom trace) vs Unfatigued Insert Pullout (top trace) Fatigued = 12,380 lbf Unfatigued = 13,380 lbf

Slide12: 

TapLok Static Pull Test Results

Results Cyclical Pull Tests for TapLok: 

Results Cyclical Pull Tests for TapLok Cycled Samples pull out strength relatively unchanged Yield strength values averaged 82% of Tensile strength Thermally cycled samples did not vary from unheated samples

Slide14: 

Shear Key Copper Threads

Shear Key Copper Threads, Static and Cyclical Testing, Test Setup: 

Shear Key Copper Threads, Static and Cyclical Testing, Test Setup

Shear Key Copper Threads, Static and Cyclical Testing: 

Shear Key Copper Threads, Static and Cyclical Testing Objective: To verify the strength of the threaded holes in the conductor for the shear key hardware under both static and fatigue conditions Test samples using conductor copper were prepared with the same hole / thread specifications as in the actual conductor Cyclical testing of copper threads was performed at room temperature

Static Pull of Copper Threads: 

Static Pull of Copper Threads A-1 12,500lbs peak, 8 Threads Pulled A-2 12,620lbs peak, 8 ½ Threads Pulled A-3 13,120lbs peak, 9 Threads Pulled A-4 12,500lbs peak, 8 Threads Pulled A-5 10,880lbs peak, 7 Threads Pulled A-6 12,380lbs peak, 8 Threads Pulled There was a strong correlation between pull out force and the number of threads pulled

Plot of Force vs Deflection Shear Key Copper Threads: 

Plot of Force vs Deflection Shear Key Copper Threads 04_24_03 Tapped Copper NO Insert A-4, Peak Force = 6.25v or 12,500lbs

Shear Key Copper Threads, Results Static: 

Shear Key Copper Threads, Results Static

Shear Key Copper Threads, Cyclical Results: 

Shear Key Copper Threads, Cyclical Results Samples pulled after cycling showed no degradation in pull out strength Pull out strength correlated with the number of threads pulled Yield Strength for both cycled and uncycled samples averaged 82% of the pullout strength Tests were performed on copper samples subjected to oven thermal cycling with no noticeable degradation to pull out strength Average pullout force for static test of threads was 12,780 lbf with a corresponding ultimate shear stress of 29.0 KPSI (compares conservatively with design allowables)

Shear Key Copper Threads, Cyclical Plot: 

Shear Key Copper Threads, Cyclical Plot Example of force vs deflection curve for cycling of inserts 7/21/03 Bare Copper Bar 2 Sample #3 (cycled at room temperature) Force = 5,010 to 6,000 lbs

Shear Key Copper Threads, Results Cyclical: 

Shear Key Copper Threads, Results Cyclical No appreciable degradation in the pull out strength of samples subjected to 50,000 cycles One sample subjected to 233,000 cycles with same result

Friction Test: 

Friction Test Objective: To characterize the COF for the flag electrical faces under varying preloads. Two horizontal load cells measure compressive force provided by eight 3/8th inch bolts Specimens are machined and plated after each run Vertical load is applied to offset middle block

Friction Tests Results, Plot: 

Friction Tests Results, Plot Plot of Force vs Distance Force is recorded at point where nonlinear behavior begins

Friction Test Results (cont.): 

Friction Test Results (cont.) Mean COF = .41 Min. Value = .39 Results consistent for varying compressive loads

Collar Shear Test: 

Collar Shear Test Objectives: To characterize the shear strength and elasticity of the TF Shear Collar both under static and fatigue conditions To correlate shear strength and clamping pressure

Collar Sample Test Setup: 

Collar Sample Test Setup Test Fixture Designed to provide compression as sample is tested in shear or cycled Dual Load Cells measure compressive load and the MTS load cell measures shear load

Plot of Shear Collar Static Sample Tests: 

Plot of Shear Collar Static Sample Tests Clamping pressure vs shear failure loads show good correlation

Static Collar Testing Result: 

Static Collar Testing Result Initial collar test consistently failed at the epoxy to steel interface Grooved plates then an improved epoxy were tested resulting in improved shear stress results (22%) and maximized system strength (failure no longer at adhesive layer) Five sets of samples tested, only sets 4 and 5 which represent the final configuration are reported on here

Test Samples, Static Tests: 

Test Samples, Static Tests Adhesive interface to steel plates is no longer the failure mode after addition of slots and improved epoxy

Plot of Shear Collar Cyclical + Static Sample Tests: 

Plot of Shear Collar Cyclical + Static Sample Tests Pink data points represent samples broken after cycling Greater scatter may be the result of shear test done at different compression than cycling

Collar Cyclical Testing Results: 

Collar Cyclical Testing Results Seven collar samples cycled at over 50,000 cycles Six of Seven samples survived four of which were cycled at elevated stress values (higher than nominal design value) One sample failed after 2,800 cycles at 1,800 psi. The clamping load on this sample was only 226 psi and the cycling rate was high, 1HZ One sample under went 233,000 cycles at 1,300 psi and low clamping load with no failure. Another sample was cycled at 1,600 psi for 123,600 cycles without failure (1,000psi clamping)

Cyclical Collar SampleTesting Data: 

Cyclical Collar SampleTesting Data